image1 image2 image3 image4
SIVAPARS

 

The SIVAPARS low-voltage switchboard is the standard solution for building and industrial technology.

As a power distribution board, SIVAPARS is available throughout the world and can be used at all power levels up to 4000 A, as withdrawable as well as plug-in and fixed mounted units.

Type Testing

The Sivapars switchgear  has  successfully  passed all the test  specified by relevant  IEC   standards in IPH  Berlin Laboratory.

 

Typical applications:

Chemicals and mineral oil industry

power center and main distribution boards

Power industry

power station and auxiliaries systems

Public/private contractors

building systems

Capital goods industry

production-oriented systems

SIVAPARS offers  advantages  that set new standards:

  • Type-tested acc. IEC 61439
  • Standardised busbar position at the top of the cubicle
  • Deep switchgear compartment for universal installation
  • Modular structure of device compartments
  • Single-front and back-to-back installation
  • Cable supply from above or below

The SIVAPARS framework and cladding system:

Frame and enclosure are manufactured from sheet steel in the following thicknesses :

  • Frame 2.5 mm
  • Enclosure 2.0 mm
  • Door 2.0 mm
  • IP 41 standard

Depending  on  the requirement, the function  areas may be subdivided as detailed in the following table:

Circuit-breaker

design

FCB1

1 ACB/cubicle

BC

1 BC (1

ACB/cubicle)

FCB2/3,

FCB2BC

2/3 ACB/cubicle

Fixed-mounted

design

OFF1

-

OFF2

OFF3

OFF4

OFFD1/2

3NJ4

Reactive power

compensation

PFC

Plug-in design

OFPD

3NJ6

OFPM

In-line plug-in

Withdrawable unit

design

OFW

Cubicle for

customized solution

CCS

 

 

Cubicle type (English)

Abbreviation

Feeder Circuit-Breaker      
For 1 circuit-breaker (fixed-mounted or withdarwable FCB1)

For 2 circuit-breaker (fixed-mounted or withdarwable FCB2)

For 3 circuit-breaker (fixed-mounted or withdarwable FCB3)

Feeder Circuit-Breaker and Bus Couplers
for 2 ciruit-breakers FCB2BC

FCB1
FCB2
FCB3

FCB2BC

Bus Couplers

for circuit-breakers (fixed-mounted or withdrawable)

Outgoing Feeder

Fixed-Mounted

with internal separation type 2

with internal separation type 4

with internal separation type 3 / 4

cable connection at rear, BS

with internal separation type 3 / 4

cable connection at front, BS

in-line disconnectors 3NJ4 up to 160 A

in-line disconnectors 3NJ4 up to 630 A

Plug-In

in-line disconnectors

Power Factor Correction Cubicles

Fixed-Mounted

OFF1

OFF2

OFF3

OFF4

OFFD1

OFFD2

OFPD

PFC

Cubicles for Customized Solutions

CCS

Outgoing Feeder

Plug-In

plug-in modules

Withdrawable

Corner Cubicles  CC

OFPM

OFW

CC

 

 

Low Voltage Switchgear SIVAPARS

Technical Information

Reference Standards

Type-tested Switchgear and Controlgear Assembly

IEC-61439-1 (2009-01) ,IEC 61439-2 (2009-01)

IEC 60529 (2001-02)

Electrical

Rated Voltage

Rated impulse withstand voltage

Rated insulation voltage

Rated operational voltage

Max. Test Voltage

Uimp = 8 kV

Ui = 1000 V

Ue = up to 690 V

2200 V, 5 Sec

Rated Currents

Main Horizontal Busbars

Rated current

Rated peak withstand current

Rated short-time withstand current

Vertical Busbars Fixed System

Rated current

Rated peak withstand current

Rated short-time withstand current

Vertical Busbars

Removable & Withdrawable system

Rated current

Rated peak withstand current

Rated short-time withstand current

In = 4000A

Ipk = 250 kA

Icw = 100 kA, 1s

In = 4000A

Ipk = 250 kA

Icw = 100 kA, 1s

In=1200A

Ipk = 163 kA

Icw = 65 kA, 1s

Mechanical

Internal Separation

IEC 61439-2 (2009-01)

Sub clause 8.101 Annex AA

Degree or Protection

IEC 60529

IP 2X up to IP 41

Materials

Doors

Framework

Mounting plates

Rear Plates

Top Plates

Gland Plates

Painted steel 2 mm

Galvanized sheet 2.5mm

Galvanized sheet 2 or 2.5mm

Galvanized sheet 2mm

Galvanized sheet 1 and 2.5mm

Galvanized sheet 2mm

Color

Doors

RAL 7032

RAL 7035

Dimensions (mm)

Height

Width

Depth

2200

400, 600, 800, 1000

600, 800, 1000, 1200

Service Conditions

Installation

Ambient Temperature

Relative Humidity

Altitude

Internal(Indoor)

+5  to +40°C

10%  to 98% at 50°C

2200 m with load reduction factor 0.88